3.1 PHASE CONTROL FLUX PLATE VARILUMDP
 

  Productsearch:  


Click to see a larger image
(Illustration similar)
 

3.1.2 ESPVAR020P – „Leading-edge phase dimmer VARILumDP 20A, single-phase“ EN

Product Description
  • Fully electronic, single-phase leading-edge phase dimmer for resistive and ohmic loads such as uncompensated discharge lamps, incandescent lamps, etc.
  • Optimized for use in tunnel lighting systems
  • Automatic warm up phase when the controller is switched on
  • Adjustable minimum current monitoring during the warm up phase
  • Regulating time delay for negative set value changes
  • Luminous flux limit values Φmax and Φmin can be set
  • Override input for bypass operation
  • Built-in simulator
  • PROFIBUS DP interface for control and configuration
  • Additional analogue control and analogue actual value output
Your advantages
  • Accurate adjustment of the luminance to the actual requirements
  • Energy savings through compensation of planning reserves
  • Safety gain through possible autotracking in case of luminous flux decrease (e.g. lamp ageing)
  • No moving parts that need servicing
  • High efficiency

Technical specifications
Electrical properties
Input voltage 230V AC ± 15%, 45...63 Hz
Permanent load current 20A ohmic or ohmic-inductive load
Control Load-independent U²-control
Connection Single-phase mode, star-connection with neutral wire
Power dissipation ≈ Pv = 20 W + 1,3 V x ILast
Device fuse Flipping-fast semiconductor fuse
Input signal Current signal: Burden 50 Ω / Voltage signal: 25 kΩ
Actual value output signal Current signal: Burden max. 500 Ω / Voltage signal: max. 20 mA
Display and measurement accuracies Load current, load voltage, analogue input / output: ±1 %
Mains voltage: ±2,5 %
Electric power: ±2 %

Electrical connection

Control wires: Via screw terminals for cable cross sections 0.2...2.5 mm²
Load wires: Via cable lugs (DIN 46 212)
Fault signalling contact Relay  1 x change over contact, 1 A / 230 V AC, ohmic load

Electromagnetic compatibility

According to DIN EN 61326-1
Emissions: Class A – only for industrial applications
Immunity: Suitable for industrial applications
Insulation test voltage  According to EN 50 178
   

Physical properties

 
Housing Plastic with anodised heat sink
Dimensions B × H × D = 45 × 155 × 150 mm
Protection degree IP 20
Weight 1,10 kg
Mounting position Vertical
Cooling Natural convection
Temperature range Storage temperature: -10°...+70° C
Ambient temperature 0°...+45° C
 
To the Instructions: (click)

Click to see a larger image
(Illustration similar)
 

3.1.4 ESPVAR032P – „Leading-edge phase dimmer VARILumDP 32A, single-phase“ EN

Product Description
  • Fully electronic, single-phase leading-edge phase dimmer for resistive and ohmic loads such as uncompensated discharge lamps, incandescent lamps, etc.
  • Optimized for use in tunnel lighting systems
  • Automatic warm up phase when the controller is switched on
  • Adjustable minimum current monitoring during the warm up phase
  • Regulating time delay for negative set value changes
  • Luminous flux limit values Φmax and Φmin can be set
  • Override input for bypass operation
  • Built-in simulator
  • PROFIBUS DP interface for control and configuration
  • Additional analogue control and analogue actual value output
Your advantages
  • Accurate adjustment of the luminance to the actual requirements
  • Energy savings through compensation of planning reserves
  • Safety gain through possible autotracking in case of luminous flux decrease (e.g. lamp ageing)
  • No moving parts that need servicing
  • High efficiency

Technical specifications
Electrical properties
Input voltage 230V AC ± 15%, 45...63 Hz
Permanent load current 32 A ohmic or ohmic-inductive load
Control Load-independent U²-control
Connection Single-phase mode, star-connection with neutral wire
Power dissipation ≈ Pv = 20 W + 1,3 V x ILast
Device fuse Flipping-fast semiconductor fuse
Input signal Current signal: Burden 50 Ω / Voltage signal: 25 kΩ
Actual value output signal Current signal: Burden max. 500 Ω / Voltage signal: max. 20 mA
Display and measurement accuracies Load current, load voltage, analogue input / output: ±1 %
Mains voltage: ±2,5 %
Electric power: ±2 %

Electrical connection

Control wires: Via screw terminals for cable cross sections 0.2...2.5 mm²
Load wires: Via cable lugs (DIN 46 212)
Fault signalling contact Relay  1 x change over contact, 1 A / 230 V AC, ohmic load

Electromagnetic compatibility

According to DIN EN 61326-1
Emissions: Class A – only for industrial applications
Immunity: Suitable for industrial applications
Insulation test voltage  According to EN 50 178
   

Physical properties

 
Housing Plastic with anodised heat sink
Dimensions B × H × D = 60 × 200 × 180 mm
Protection degree IP 20
Weight 2,80 kg
Mounting position Vertical
Cooling Natural convection
Temperature range Storage temperature: -10°...+70° C
Ambient temperature 0°...+45° C
 
To the Instructions: (click)

Click to see a larger image
(Illustration similar)
 

3.1.6 ESPVAR050P – „Leading-edge phase dimmer VARILumDP 50A, single-phase“ EN

Product Description
  • Fully electronic, single-phase leading-edge phase dimmer for resistive and ohmic loads such as uncompensated discharge lamps, incandescent lamps, etc.
  • Optimized for use in tunnel lighting systems
  • Automatic warm up phase when the controller is switched on
  • Adjustable minimum current monitoring during the warm up phase
  • Regulating time delay for negative set value changes
  • Luminous flux limit values Φmax and Φmin can be set
  • Override input for bypass operation
  • Built-in simulator
  • PROFIBUS DP interface for control and configuration
  • Additional analogue control and analogue actual value output
Your advantages
  • Accurate adjustment of the luminance to the actual requirements
  • Energy savings through compensation of planning reserves
  • Safety gain through possible autotracking in case of luminous flux decrease (e.g. lamp ageing)
  • No moving parts that need servicing
  • High efficiency

Technical specifications
Electrical properties
Input voltage 230V AC ± 15%, 45...63 Hz
Permanent load current 50 A ohmic or ohmic-inductive load
Control Load-independent U²-control
Connection Single-phase mode, star-connection with neutral wire
Power dissipation ≈ Pv = 20 W + 1,3 V x ILast
Device fuse Flipping-fast semiconductor fuse
Input signal Current signal: Burden 50 Ω / Voltage signal: 25 kΩ
Actual value output signal Current signal: Burden max. 500 Ω / Voltage signal: max. 20 mA
Display and measurement accuracies Load current, load voltage, analogue input / output: ±1 %
Mains voltage: ±2,5 %
Electric power: ±2 %

Electrical connection

Control wires: Via screw terminals for cable cross sections 0.2...2.5 mm²
Load wires: Via cable lugs (DIN 46 212)
Fault signalling contact Relay  1 x change over contact, 1 A / 230 V AC, ohmic load

Electromagnetic compatibility

According to DIN EN 61326-1
Emissions: Class A – only for industrial applications
Immunity: Suitable for industrial applications
Insulation test voltage  According to EN 50 178
   

Physical properties

 
Housing Plastic with anodised heat sink
Dimensions B × H × D = 80 × 200 × 195 mm
Protection degree IP 20
Weight 2,80 kg
Mounting position Vertical
Cooling Natural convection
Temperature range Storage temperature: -10°...+70° C
Ambient temperature 0°...+45° C
 
To the Instructions: (click)

Click to see a larger image
(Illustration similar)
 

3.1.8 ESPVAR100P – „Leading-edge phase dimmer VARILumDP 100A, single-phase“ EN

Product Description
  • Fully electronic, single-phase leading-edge phase dimmer for resistive and ohmic loads such as uncompensated discharge lamps, incandescent lamps, etc.
  • Optimized for use in tunnel lighting systems
  • Automatic warm up phase when the controller is switched on
  • Adjustable minimum current monitoring during the warm up phase
  • Regulating time delay for negative set value changes
  • Luminous flux limit values Φmax and Φmin can be set
  • Override input for bypass operation
  • Built-in simulator
  • PROFIBUS DP interface for control and configuration
  • Additional analogue control and analogue actual value output
Your advantages
  • Accurate adjustment of the luminance to the actual requirements
  • Energy savings through compensation of planning reserves
  • Safety gain through possible autotracking in case of luminous flux decrease (e.g. lamp ageing)
  • No moving parts that need servicing
  • High efficiency

Technical specifications
Electrical properties
Input voltage 230V AC ± 15%, 45...63 Hz
Permanent load current 100 A ohmic or ohmic-inductive load
Control Load-independent U²-control
Connection Single-phase mode, star-connection with neutral wire
Power dissipation ≈ Pv = 20 W + 1,3 V x ILast
Device fuse Flipping-fast semiconductor fuse
Input signal Current signal: Burden 50 Ω / Voltage signal: 25 kΩ
Actual value output signal Current signal: Burden max. 500 Ω / Voltage signal: max. 20 mA
Display and measurement accuracies Load current, load voltage, analogue input / output: ±1 %
Mains voltage: ±2,5 %
Electric power: ±2 %

Electrical connection

Control wires: Via screw terminals for cable cross sections 0.2...2.5 mm²
Load wires: Via cable lugs (DIN 46 212)
Fault signalling contact Relay  1 x change over contact, 1 A / 230 V AC, ohmic load

Electromagnetic compatibility

According to DIN EN 61326-1
Emissions: Class A – only for industrial applications
Immunity: Suitable for industrial applications
Insulation test voltage  According to EN 50 178
   

Physical properties

 
Housing Plastic with anodised heat sink
Dimensions B × H × D = 100 × 200 × 221 mm
Protection degree IP 20
Weight 3,70 kg
Mounting position Vertical
Cooling Natural convection
Temperature range Storage temperature: -10°...+70° C
Ambient temperature 0°...+45° C
 
To the Instructions: (click)